Voltage Converter

The Voltage Converter is a cost-effective way of converting 24 VAC or VDC to 5, 12, 15, or 24 VDC for use on peripheral devices that require DC voltage. The converter is available with a 350 mA output. The mounting system allows for 2.75” snaptrack, DIN rail or surface mounting.

It is often desirable to convert to DC power as it eliminates the AC power “noise” which can affect the room sensor readings. Tests show that fluctuating and inaccurate signal levels are possible when AC power wiring is present in the same cable as the signal lines. To minimize the AC voltage noise, the DC converter must be mounted as close to the controller as physically possible. Do not mount the converter at the sensor end of the wire, the AC will still couple into the sensor signal if you do.

Part Number and Description
Part Number Description
NSB-VC350A-EZ-ADJ-A 5 to 24 VDC Adjustable Output at 350 mA
Specifications
  • Output Voltage: 5 to 24 VDC @ 350 mA
  • Recommended Input Voltage: 18 to 28 VAC, 24 VDC (15 VA)
  • Environmental Storage Range: -40 to 176°F (-40 to 80°C)
  • Environmental Operation Range:
    0 to 95% RH non-condensing
    -40 to 149°F (-40 to 65°C) 350 mA @ any output voltage
    -40 to 158°F (-40 to 70°C) 350 mA @ 5 VDC
    330 mA @ 10 VDC
    280 mA @ 12 VDC
    224 mA @ 15 VDC
    140 mA @ 24 VDC
  • Wiring: 4 wires, 16 to 22 gauge
  • Rectification: Half-Wave Rectified
  • Grounding: AC & DC Ground are Common
  • Input Voltage Limits:
Minimum
(VAC/VDC)
Maximum
(VAC/VDC)
Input Current@
Min Input Volts(AC/DC)
24.0/31.0* 28.0/35.0 16.7 VA/325 mA

*Depends on output voltage

Part Number Description
NSB-VC350A-EZ-ADJ-A 5 to 24 VDC Adjustable Output at 350 mA
  • Output Voltage: 5 to 24 VDC @ 350 mA
  • Recommended Input Voltage: 18 to 28 VAC, 24 VDC (15 VA)
  • Environmental Storage Range: -40 to 176°F (-40 to 80°C)
  • Environmental Operation Range:
    0 to 95% RH non-condensing
    -40 to 149°F (-40 to 65°C) 350 mA @ any output voltage
    -40 to 158°F (-40 to 70°C) 350 mA @ 5 VDC
    330 mA @ 10 VDC
    280 mA @ 12 VDC
    224 mA @ 15 VDC
    140 mA @ 24 VDC
  • Wiring: 4 wires, 16 to 22 gauge
  • Rectification: Half-Wave Rectified
  • Grounding: AC & DC Ground are Common
  • Input Voltage Limits:
Minimum
(VAC/VDC)
Maximum
(VAC/VDC)
Input Current@
Min Input Volts(AC/DC)
24.0/31.0* 28.0/35.0 16.7 VA/325 mA

*Depends on output voltage