“We had a lot of fun setting up that building,” Joyce remarked. With technical and custom graphics support from Logical Control Solutions, Joyce’s Department of Utilities and Energy Management partnered with the University’s HVACR shop which designed, programmed and installed the system. A total of 90 labs were outfitted with Phoenix Controls VAV fume hood sash position controls and venturi-style VAV boxes, digital room controllers, reheat valve transducers, room occupancy sensors and user-adjustable networked thermostats. Another 100 non-fume hood labs were retrofitted with box-mounted Automated Logic controls, room occupancy sensors, thermostats and reheat controls.
“With WebCTRL’s ease of programming, we were able to commission three to four fume hood labs over an eight-hour shift,” Joyce noted. And because the labs needed to remain operational in the 24/7 facility, most of the work was completed overnight.
Results following the installation were both immediate and dramatic. “Our control strategy was to minimize air change rate in the room to what was necessary to keep it comfortable and provide a safe working environment,” Joyce continued. “We were able to cut the minimum ventilation rate in half when a room is unoccupied, and we relaxed unoccupied setpoints from ±1.5 to ±3.0 during scheduled occupied hours and to ±6.0 during unoccupied hours. On an annual basis, that’s a big energy savings.” University officials also launched an energy savings and lab safety program for building users, encouraging them to close VAV hoods when not in use. Combined with the WebCTRL retrofit, efforts have saved nearly $350,000 annually in building energy costs.
“When we put the project together, we made estimates of our energy savings,” noted Project Manager Alan Hebert, E.E. “Our prediction at the time was about 30 percent annually with Automated Logic controls and other energy conservation improvements. We’re very close to the 27-28 percent range, and we’ll probably exceed the 30 percent savings we had estimated.”
“WebCTRL provides a higher level of programming sophistication, and at the same time, it’s much easier to use. The ease of creating and displaying trends, and of doing analysis from the trend data, allows us to verify the performance of all the algorithms we put into a building,” Joyce added.
“WebCTRL fit into our larger BACnet communication scheme at the University and tied in very well to our 24-hour operation for central alarm repository,” said Dave Roman, Project Engineer. Added Ron Hurd, Field Engineer: “WebCTRL’s tools are perfect for tracking energy consumption from long-term data storage. The tools are superior.”
In addition to those colleagues, Joyce credits Jim Obrien, HVACR shop Construction General Foreperson, and Cornell’s HVACR, electric and sheet metal shops for the successful outcome.
“It was a fantastic job, a real team effort,” he said. “And the technical support we get from Logical Control Solutions and from Automated Logic’s corporate office is key to our success with these products.” With the Biotechnology Building operating more efficiently, WebCTRL installations are underway or planned for a number of additional facilities on campus.